Coordinate CCT and color qualities (TM-30) for special applications with Engineering Services Electrical Group. Require testing to IES LM-79 and LM-80 standards and life calculations based on IES TM-21. . All LEDs shall incorporate a 4000 kelvin temperature CCT, and a minimum of 80 CRI Minimum L70 of 60,000 hours, and minimum efficacy of 90 lumens per watt.However, there are instances where fluorescent technology may be deployed where approved by Engineering Services Electrical Group. The use of LED lamps in all luminaires is highly recommended.No luminaire or lamp modification may void the UL listing. All luminaire retrofit applications shall be approved by Engineering Services Electrical Group and satisfy the requirements in this specification section. Luminaire retrofit kits shall be evaluated based on present market pricing as compared to new luminaire installations. However, the technical and performance characteristics of this section apply for each intended application of retrofit kits. Retrofit kits: Retrofit kits may be an opportunity for stewardship and sustainable design.
Penn interiors construction drivers#
Remote drivers shall be installed per manufacturer’s requirements. Consider remote mount drivers where fixture mounting heights exceed twenty (20) feet, or access to luminaires is restricted. Drivers must be rated for high temperature environment.
Penn interiors construction pdf#
Provide a PDF copy of the Luminaire cutsheets with every review submittal showing lighting layouts.
Penn interiors construction code#
10 - B Elevator Service and Support and locally adopted code for applicable illumination requirements. Provide a spreadsheet showing all room names and numbers along with target illumination levels.
Penn interiors construction full#
Utilize AGI-32 full calculation mode or Acuity Brands “Visual”.
Engineering Services Electrical Group will provide direction and variance where deemed adequate. All pertinent calculation parameters shall be indicated, highlight where the design is non-IES compliant. Point levels shall be legible, shown on a scaled drawing. The use of certain “typical” rooms shall be acceptable.
Discuss luminaire application with Engineering Services Electrical Group.